TEMPRITE ROOF TOP AIR MAKE UP UNIT #447
      Nov.23/99 Oct.6/00 Oct.15/01   Oct.19/04    
           
MAIN REGULATOR LOCKUP: 12 "wc 15.0"wc 13.0"WC 13.0"WC    
           
GAS PRESSURES Gas Supply "wc 14 13 11.7 9.44    
  Low Fire "wc -4 -4.2 -4      
    High Fire "wc 2.5 2.3 2.6   7.4    
          High Fire Low Fire High Fire Low Fire  
COMBUSTION AIR:     O2 O2% 9.2 10.1 11.2 16.7 10.8 16.4  
  CO ppm   98 161 113 6 7  
  CO2% 6.6 6.1 5.5 2.4 5.7 2.5  
  Stack F 488 453  207 C 76 C 226.7 C 226.7  
    Efficiency% 74.8 86.9 76.20% 80.70% 76.1 76.1  
                   
OVERFIRE DRAFT (high fire) "wc -0.93 -0.15 -0.18 -0.48    
           
SAFETY CUTOUTS: Low Gas "wc 2.5 OK OK OK    
  Hi Gas "wc 12 OK OK OK    
  Flame Failure (within 4 sec) OK OK OK   OK 2 sec.  
                   
SETTINGS: Roomstat C   27 24 24 75 F  
  Ductstat F   70 75   70 F  
           
COMMENTS:                
Oct.19/04 1.) Changed out downstream Fluid Power Actuator and installed new valve kit in gas valve  
  2.) New Flame Detector installed  
  3.) Adjusted air linkage to reduce CO (69 ppm) at low fire        
Oct.15/01 1.) CO was 1300 plus at low fire! Adjusted combustion air damper linkage to give more air at low fire
  2.) Adjusted supply gas regulator from 12.7 to 11.7"WC  
  3.) Down stream Fluid Power valve leaking by somewhat (no change made at this time)  
  4.) New ignition and detection electrodes installed  
  5.) Heat exchanger inspected for cracks  
  6.) Supervisory cock greased (new pilot solenoid installed last year)      
Oct.6/00  
Past Work Done:  
  Upstream Fluid Power gas valve replaced  
  Combustion Air Fan cleaned  
  Pilot solenoid valve replaced