TEMPRITE ROOF TOP AIR MAKE UP UNIT #107
      Nov.23/99 Oct.6/00 Oct.15/01   Oct.19/04  
             
MAIN REGULATOR LOCKUP: 10.5 "wc 11.6 "wc 9.9"WC   12.1"wc  
             
GAS PRESSURES Gas Supply "wc 11.5   11.3    
  Low Fire "wc -3.2 -3.4 -3.2   -3.1  
    High Fire "wc 1.4 2.5 2.55   2.48  
          High Fire Low Fire High Fire Low Fire
COMBUSTION AIR:     O2 O2% 9.3 10.6 11 17.4 10.8 17.2
  CO ppm   107 10 317 9 19
  CO2% 6.5 5.9 5.6 2 5.7 2.1
  Stack F 425 362 203 C 105 C 195.9 C 88.3 C
    Efficiency% 74.7 89.6 76.70% 73.30% 78.10% 78.90%
                 
OVERFIRE DRAFT (high fire) "wc -0.93 -0.15 -0.15   -0.15  
               
SAFETY CUTOUTS: Low Gas "wc 2.5 OK OK   OK  
  Hi Gas "wc 12 OK OK   OK  
  Flame Failure (within 4 sec) OK OK OK   OK  
SETTINGS: Roomstat C   20 21   20 68 F
    Ductstat F   62 64     64 F
COMMENTS:  
Oct.19/04 1.) Adjusted air linkage to eliminate very high CO (1000+) at low fire. Linkage had become loose.
  2.) MU Fan switched from Auto to Manual  
   
Oct.15/01 1.) Pilot Solenoid leaking by  
  2.) New detector installed  
  3.) Supervisory Cock greased  
Oct.6/00 Supervisory gas cock (plug) leaking by - regrease  
  Roomstat was cleaned with contact cleaner  
Past Work Done:  
  Upstream Fluid Power Actuator changed out