TEMPRITE ROOF TOP AIR MAKE UP UNIT
#107 |
|
|
|
|
|
|
|
|
|
|
|
|
Nov.23/99 |
Oct.6/00 |
Oct.15/01 |
|
Oct.19/04 |
|
|
|
|
|
|
|
|
|
|
|
|
MAIN
REGULATOR LOCKUP: |
10.5 "wc |
11.6 "wc |
9.9"WC |
|
12.1"wc |
|
|
|
|
|
|
|
|
|
|
|
|
GAS PRESSURES |
Gas Supply "wc |
11.5 |
|
11.3 |
|
|
|
|
|
|
Low Fire "wc |
-3.2 |
-3.4 |
-3.2 |
|
-3.1 |
|
|
|
|
High Fire "wc |
1.4 |
2.5 |
2.55 |
|
2.48 |
|
|
|
|
|
|
|
High Fire |
Low Fire |
High Fire |
Low Fire |
|
COMBUSTION AIR: O2 |
O2% |
9.3 |
10.6 |
11 |
17.4 |
10.8 |
17.2 |
|
|
|
CO ppm |
|
107 |
10 |
317 |
9 |
19 |
|
|
|
CO2% |
6.5 |
5.9 |
5.6 |
2 |
5.7 |
2.1 |
|
|
|
Stack F |
425 |
362 |
203 C |
105 C |
195.9 C |
88.3 C |
|
|
|
Efficiency% |
74.7 |
89.6 |
76.70% |
73.30% |
78.10% |
78.90% |
|
|
|
|
|
|
|
|
|
|
|
OVERFIRE
DRAFT (high fire) "wc |
-0.93 |
-0.15 |
-0.15 |
|
-0.15 |
|
|
|
|
|
|
|
|
|
|
|
|
SAFETY CUTOUTS: |
Low Gas "wc |
2.5 |
OK |
OK |
|
OK |
|
|
|
|
Hi Gas "wc |
12 |
OK |
OK |
|
OK |
|
|
|
Flame
Failure (within 4 sec) |
OK |
OK |
OK |
|
OK |
|
|
SETTINGS: |
Roomstat C |
|
20 |
21 |
|
20 |
68 F |
|
|
|
Ductstat F |
|
62 |
64 |
|
|
64 F |
|
COMMENTS: |
|
|
|
Oct.19/04 |
1.)
Adjusted air linkage to eliminate very high CO (1000+) at low fire. Linkage
had become loose. |
|
|
2.) MU Fan switched from
Auto to Manual |
|
|
|
|
|
|
|
|
Oct.15/01 |
1.) Pilot Solenoid leaking by |
|
|
|
|
|
2.) New detector installed |
|
|
|
|
|
3.) Supervisory Cock greased |
|
|
|
|
Oct.6/00 |
Supervisory gas cock (plug) leaking
by - regrease |
|
|
|
|
Roomstat was cleaned with contact
cleaner |
|
|
|
Past Work Done: |
|
|
|
|
Upstream Fluid Power Actuator
changed out |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|