TEMPRITE ROOF TOP AIR MAKE UP UNIT #103
      Nov.23/99 Oct.6/00 Oct.15/01   Oct.19/04  
#103            
MAIN REGULATOR LOCKUP: 11.75 "wc 11.88 "wc N/A   11.3  
             
GAS PRESSURES Gas Supply "wc 11 10.92 10.1   10.6  
  Low Fire "wc -1.5 -1.4 1.52      
  High Fire "wc 2 2.12 2.1      
        High Fire Low Fire High Fire Low Fire
COMBUSTION AIR: O2% 7.5 8.1 8.1 15.7 8.4 15.6
  Coppm   93 28 114 6 6
  CO2% 7.6 7.3 7.3 3 7.1 3
  Stack F 393 410 183 C 98 C 226.8 C 108.5
  Efficiency% 82.7 89.8 80.40% 79.60% 78.50% 79.90%
             
OVERFIRE DRAFT (high fire) "wc -0.41 0.38 0.41   -1.18  
             
SAFETY CUTOUTS: Low Gas "wc 2.5 OK OK   OK  
  Hi Gas "wc 12 OK OK   OK  
  Flame Failure (within 4 sec) OK OK N/A   OK  
             
SETTINGS: Roomstat C   20 21   18 (64 F)
  Ductstat F   62 64   59  
                 
COMMENTS:
Oct.19/04 1.) Overfire draft high ( -1.18 )  No adjustments made at this time.
Oct.15/01 1.) New Burner Drawer installed (pilot tube rusted completely off)
2.) Still have positive overfire draft - clean and inspect ID Fan & damper
3.) Pilot solinoid leaking by (suspect this is the reason for pilot burnout)
4.) Supervisory cock greased
5.) New detector and Ignition electrodes installed
6.) Could not do regulator lockup reading as couldn't flame out the burner
Oct.6/00 Supervisory gas cock (plug) leaking by - regrease
ID Fan outlet damper seized
Possitive overfire draft at high fire- should adjust damper linkage and gas appl. reg.
Should remove and clean ID Fan
Modutrol is not responding to Ductstat ….replace ductstat
Past Work Done:
Upstream Fluid Power gas valve body replaced