TEMPRITE ROOF TOP AIR MAKE UP UNIT #101      
     
      Nov.23/99 Oct.6/00 Oct.15/01   Oct.19/04  
#101              
                 
MAIN REGULATOR LOCKUP: 11.5"wc 13.0"wc 10.45   11.5  
                 
GAS PRESSURES Gas Supply "wc 12 9.7 11.05   10.44  
  Low Fire "wc -4.5 -2.4 -2.45   -3.22  
  High Fire "wc 1.5 1.45 1.55   1.37  
          High Fire Low Fire High Fire Low Fire
COMBUSTION AIR:     O2% 6.1 8.6 8.5 14.8 8.5 14.3
  CO%   88 12 10 4 8
  CO2% 8.4 7 7 3.4 7 3.7
  Stack F 475 425 209 C 138 C 217 C 136.2 C
  Efficiency% 77.3 89.1 78.70% 76.40% 78.80% 78.80%
                 
OVERFIRE DRAFT (high fire) "wc -0.21 -0.58 -0.2   -0.68  
               
SAFETY CUTOUTS: Low Gas "wc   OK OK   OK  
  Hi Gas "wc   OK OK   OK  
  Flame Failure (within 4 sec) OK OK OK   OK  
               
SETTINGS: Roomstat C   20 21   22  
    Ductstat F   62 64   67  
COMMENTS:              
Oct.19/04 1.) Unit would not start. Roomstat faulty …. Changed out for a new unit    
  2.) Water leaking into control cabinet (freezestat found full of water)  
  3.) New detector installed  
  4.) High CO at low fire (114 ppm)  - Linkage adjusted to give less air & better mixing  
Oct.15/01 1.) Supply gas pressure falling off since 1999 - readjusted Reg. To give 11.05"WC.  
  2.) Pilot solenoid leaking by  
  3.) Greased supervisory cock  
  4.) New detector electrode installed          
Oct.6/00 - new burner Drawer Assembly installed with new detector and ignitor  
  ID Fan proving switch sensing tube needs replacing  
  Adjusted hi-gas cutout to 12"wc  
  Rubber expansion joint on plenum to furnace needs replacing - done!  
   
   
Past Work Done: